This fix system vertical busbar support, MSFH, for two bars up to 40 x 10 mm, is available off the shelf and has been tested according to IEC 61439.
Thanks for your submission. A customer service agent will be in touch soon to help you further.
Details
Leistungen
Ressourcen
Zubehör
Merkmale
- Description: Busbar supports up to 1600A to be mounted vertically behind the fixed compartments. Mounts to the vertical profiles MSFP. Rated short-time withstand current up to 35 kA with rear supports and up to 50 kA with rear and front supports.
- Material: Polycarbonate reinforced with 10% of glass material.
- Delivery: 7 busbar supports for 3 phases and neutral, and mounting material.
- A flexible and reliable solution that ensures procurement, design and installation can be done efficiently reducing the labour time required
- Fix system vertical profiles (MSFP) are required in order to mount the busbar supports
- Busbar supports up to 1600A to be mounted vertically behind the fixed compartments
- Mounts to the vertical profiles MSFP
- Rated short-time withstand current up to 35 kA with rear supports and up to 50 kA with rear and front supports
- Delivery: 7 busbar supports for 3 phases and neutral, and mounting material
Spezifikationen
Installationshandbuch/Kurzanleitung
Mandatory
- Warnung
- nVent-Produkte müssen in Übereinstimmung mit den Produktinformationsblättern und dem Schulungsmaterial von nVent installiert und verwendet werden. Informationsblätter sind verfügbar unter www.nVent.com sowie bei Ihrem nVent-Kundendienstvertreter. Unsachgemäße Installation, Missbrauch, Fehlanwendung oder andere Handlungen im Widerspruch zu den Anweisungen und Warnungen von nVent können zu Fehlfunktionen, Anlagenschäden, schwerer Körperverletzung sowie zum Tod führen und/oder haben die Annullierung der Garantie zur Folge.