GEM Ground Enhancement Material
Ground Enhancement Material (GEM) is a superior conductive material that solves your toughest grounding problems. It is the ideal material to use in areas of poor conductivity, such as rocky ground, mountain tops and sandy soil. GEM dramatically reduces earth resistance and impedance measurements. Furthermore, GEM may reduce the size of the grounding system where conventional methods are unsatisfactory. Once installed, GEM is maintenance-free, not requiring periodic charging or the presence of water to maintain its conductivity.
Third-party testing has been completed to verify that GEM conforms to IEC® 62561-7. This standard introduces a benchmark for electrical performance and corrosion of earth enhancement materials that has been absent from the industry to date.
nVent ERICO offers GEM Calculator software that provides resistivity values for common GEM applications and can help estimate the amount of GEM required for an installation. It operates in four languages - English, Spanish, French and German - and performs calculations in Imperial or Metric units. The GEM Calculator is available for download on our website at erico.com.
Features
- Maintains constant resistance for the life of the system once in its set form
- Performs in all soil conditions even during dry spells
- Does not require periodic charging treatments or placement
- Does not require the continuous presence of water to maintain its conductivity
- Fully sets within 3 days, fully cures within 28 days
- Does not dissolve, decompose, or leach out with time
- Non-corrosive
- Reduces vandalism and theft since conductors are hard to remove from concrete
- Easy-to-handle 25 lb (11.3kg) bags or buckets
- Requires only one person to install
- Exceeds IEC® 62561-7 which sets the benchmark for corrosion, leaching, sulfur content, and other environmental regulations
- Complies to the U.S. Environmental Protection Agency (EPA) Toxicity Characteristic Leaching Procedure (TCLP), EPA test method 1311
- Can be installed using trench or ground rod backfill methods
Specifications
Unit Weight | 11.36 kg |
Unit Weight | 25 lb |
Piedi lineari stimati del rivestimento del conduttore di terra con ciascun sacco di GEM | |||
Larghezza trincea | Spessore totale di GEM | ||
10.2 cm | 12.7 cm | 15.2 cm | |
10 cm | 1.0 m | 0.8 m | 0.7 m |
15.2 cm | 0.7 m | 0.5 m | 0.4 m |
20.3 cm | 0.5 m | 0.4 m | 0.3 m |
25.4 cm | 0.4 m' | 0.3 m | 0.3 m |
30.5 cm | 0.3 m | 0.3 m | 0.2 m |
Specifiche suggerite | ||
Parametro | Valori raccomandati | Metodo di prova |
Conformità agli standard | Piena conformità a IEC 62561-7 EPA Procedura di lisciviazione Procedura (TCLP), metodo di prova 1311 | |
Lisciviazione | Arsenico < 1,5 mg/L, Bario < 60 mg/L, Cadmio < 0,15 mg/L, Cromo < 3,0 mg/L, Piombo < 1,5 mg/L, Mercurio < 0,06 mg/L, Selenio < 1,0 mg/L | EC 62561-7 EN 12457-2 |
Contiene zolfo | < 2% | ISO 14869-1 |
Resistività | <2 Ω-cm per polvere <20 Ω-cm per materiale miscelato e polimerizzato | Polvere compressa secondo ASTM G187-12 Miscelato e polimerizzato secondo ASTM D991-89 |
Prestazioni di corrosione | Per gli elettrodi di messa a terra rivestiti in rame, la resistenza alla polarizzazione deve essere > 8 Ω x m2 per gli ambienti aggressivi Per gli elettrodi di messa a terra zincati, la resistenza alla polarizzazione deve essere > 7,6Ω x m2 per gli ambienti aggressivi | IEC 62561-7, Sezione 5.5, ambiente aggressivo |
Resistenza alla flessione | 300-450 psi [2070-3100 kPa] | ASTM C293 |
Resistenza alla compressione | 100-200 psi [690-1390 kPa] dopo 672 ore di polimerizzazione | ASTM C109 |
Sacchi stimati di GEM per riempimento intorno ai picchetti di terra a una densità di 63,5 lb/ft ³ (1,017 kg/m³) | |||||||||||||
Diametro del foro | ft | m | ft | m | ft | m | ft | m | ft | m | ft | m | |
Pollici | Centimetri | 5 | 1.5 | 6 | 1.8 | 8 | 2.4 | 10 | 3 | 15 | 4.6 | 20 | 6.1 |
4 | 10.2 | 2 | 2 | 2 | 3 | 4 | 5 | ||||||
6 | 15.2 | 3 | 3 | 4 | 5 | 8 | 10 | ||||||
8 | 20.3 | 5 | 6 | 8 | 9 | 14 | 18 | ||||||
10 | 25.4 | 7 | 9 | 12 | 14 | 21 | 28 | ||||||
12 | 30.5 | 10 | 12 | 16 | 20 | 30 | 40 |
Brochure
Catalog
Data Sheet
Installation Manual / Instruction Sheet
Technical Handbook
Certifications
- Warning
- nVent products shall be installed and used only as indicated in nVent's product instruction sheets and training materials. Instruction sheets are available at www.nvent.com and from your nVent customer service representative. Improper installation, misuse, misapplication or other failure to completely follow nVent's instructions and warnings may cause product malfunction, property damage, serious bodily injury and death and/or void your warranty.