GEM Ground Enhancement Material
Ground Enhancement Material (GEM) is a superior conductive material that solves your toughest grounding problems. It is the ideal material to use in areas of poor conductivity, such as rocky ground, mountain tops and sandy soil. GEM dramatically reduces earth resistance and impedance measurements. Furthermore, GEM may reduce the size of the grounding system where conventional methods are unsatisfactory. Once installed, GEM is maintenance-free, not requiring periodic charging or the presence of water to maintain its conductivity.
Third-party testing has been completed to verify that GEM conforms to IEC® 62561-7. This standard introduces a benchmark for electrical performance and corrosion of earth enhancement materials that has been absent from the industry to date.
nVent ERICO offers GEM Calculator software that provides resistivity values for common GEM applications and can help estimate the amount of GEM required for an installation. It operates in four languages - English, Spanish, French and German - and performs calculations in Imperial or Metric units. The GEM Calculator is available for download on our website at erico.com.
Features
- Maintains constant resistance for the life of the system once in its set form
- Performs in all soil conditions even during dry spells
- Does not require periodic charging treatments or placement
- Does not require the continuous presence of water to maintain its conductivity
- Fully sets within 3 days, fully cures within 28 days
- Does not dissolve, decompose, or leach out with time
- Non-corrosive
- Reduces vandalism and theft since conductors are hard to remove from concrete
- Easy-to-handle 25 lb (11.3kg) bags or buckets
- Requires only one person to install
- Exceeds IEC® 62561-7 which sets the benchmark for corrosion, leaching, sulfur content, and other environmental regulations
- Complies to the U.S. Environmental Protection Agency (EPA) Toxicity Characteristic Leaching Procedure (TCLP), EPA test method 1311
- Can be installed using trench or ground rod backfill methods
Specifications
Unit Weight | 11.360 kg |
Unit Weight | 25 lb |
Geschatte lengte (in voet) afdekking aardinggeleider met elke zak GEM | |||
Sleufbreedte | Totale dikte GEM | ||
10.2 cm | 12.7 cm | 15.2 cm | |
10 cm | 1.0 m | 0.8 m | 0.7 m |
15.2 cm | 0.7 m | 0.5 m | 0.4 m |
20.3 cm | 0.5 m | 0.4 m | 0.3 m |
25.4 cm | 0.4 m' | 0.3 m | 0.3 m |
30.5 cm | 0.3 m | 0.3 m | 0.2 m |
Aanbevolen specificaties | ||
Parameter | Aanbevolen waarden | Testmethode |
Voldoen aan normen | Volledig conform IEC 62561-7 EPA Toxiciteit Karakteristieke uitloging Procedure (TCLP), testmethode 1311 | |
Uitloging | Arsenicum < 1.5 mg/L, Barium < 60 mg/L, Cadmium < 0.15 mg/L, Chroom < 3.0 mg/L, Lood < 1.5 mg/L, Kwik < 0.06 mg/L, Elenium < 1.0 mg/L | EC 62561-7 EN 12457-2 |
Zwavelgehalte | < 2% | ISO 14869-1 |
Soortelijke weerstand | <2 Ω-cm voor poeder <20 Ω-cm voor gemengd en uitgehard materiaal | Gecomprimeerd poeder conform ASTM G187-12 Gemengd en uitgehard conform ASTM D991-89 |
Prestaties op corrosiegebied | Voor verkoperde aardingselektrodes, moet de polarisatieweerstand > 8 Ω x m2 bedragen voor agressieve omgevingen Voor gegalvaniseerde aardingselektrodes, moet de polarisatieweerstand > 7.6Ω x m2 voor agressieve omgevingen | IEC 62561-7, sectie 5.5, agressieve omgeving |
Buigsterkte | 300-450 psi [2070-3100 kPa] | ASTM C293 |
Druksterkte | 100-200 psi [690-1390 kPa] na 672 uur uitharden | ASTM C109 |
Geschat aantal zakken GEM voor opvullen rondom aardingspennen tot een dichtheid van 63,5 lb/voet ³ (1,017 kg/m³) | |||||||||||||
Gatdiameter | voet | m | voet | m | voet | m | voet | m | voet | m | voet | m | |
Inches | Centimeters | 5 | 1.5 | 6 | 1.8 | 8 | 2.4 | 10 | 3 | 15 | 4.6 | 20 | 6.1 |
4 | 10.2 | 2 | 2 | 2 | 3 | 4 | 5 | ||||||
6 | 15.2 | 3 | 3 | 4 | 5 | 8 | 10 | ||||||
8 | 20.3 | 5 | 6 | 8 | 9 | 14 | 18 | ||||||
10 | 25.4 | 7 | 9 | 12 | 14 | 21 | 28 | ||||||
12 | 30.5 | 10 | 12 | 16 | 20 | 30 | 40 |
Brochure
Catalog
Data Sheet
Flyer
Installation Manual / Instruction Sheet
Technical Handbook
Certifications
- Warning
- nVent products shall be installed and used only as indicated in nVent's product instruction sheets and training materials. Instruction sheets are available at www.nvent.com and from your nVent customer service representative. Improper installation, misuse, misapplication or other failure to completely follow nVent's instructions and warnings may cause product malfunction, property damage, serious bodily injury and death and/or void your warranty.